Converters:I-P converters and P-I converters.

Converters

The most common process control arrangement is probably electronic controllers with pneumatic actuators and transducers. Devices are therefore needed to convert between electrical analog

Process control pneumatics-0209

signals and the various pneumatic standards. Electrical to pneumatic conversion is performed by an 1-P converter, while pneumatic to electrical conversion is performed by a device called, not surpris­ingly, a P-1 converter.

1-P converters

Figure 7.25 illustrates a common form of 1-P converter based on the familiar force balance principle and the flapper-nozzle. Electrical current is passed through the coil and results in a rota­tional displacement of the beam. The resulting pressure change at the flapper-nozzle gap is volume-boosted by the air relay and applied as a balancing force by bellows at the other end of the beam. A balance results when the force from the bellows (propor­tional to output pressure) equals the force from the coil (propor­tional to input electrical signal).

Process control pneumatics-0210

P-I converters

The operation of a P-1 converter. illustrated in Figure 7.26 again uses the force balance principle. The input pressure signal is applied to bellows and produces a deflection of the beam. This deflection is measured by a position transducer such as an LVDT (linear variable

Process control pneumatics-0211

differential transformer). The electrical signal corresponding to the deflection is amplified and applied as current through a coil to produce a torque which brings the beam back to the null position. At balance, the coil force (proportional to output current) matches the force from the bellows (proportional to input signal pressure).

The zero offset (4 rnA) in the electrical signal is sufficient to drive the amplifier in Figure 7.26, allowing the two signal wires to also act as the supply lines. This is known as two-wire operation. Most P-1 converters operate over a wide voltage range (eg, 15 to 30 V). Often, the current signal of 4 to 20 rnA is converted to a voltage signal (commonly in the range 1 to 5 V) with a simple series resistor.

Incoming search terms:

Related posts:

Financial justification:Life cycle cost (LCC)
Air flow rate evaluation:Stepped pipeline systems
Health and safety:Conveying operations
First approximation design methods:Empirical relationships
Material property influences:Dense phase sliding bed flow
COMPRESSORS:Liquid Seal Ring Compressors
Control components in a hydraulic system:Manifolds
Pressure and flow:Fluid types
Application notes: Speed control ,Actuator synchronisation.
Pump types:Gear pumps ,Vane pumps,Piston pumps and Combination pumps.
Air Compressors, Air Treatment and Pressure Regulation:air receivers and compressor control
Safety, Fault-Finding and Maintenance:computer simulation
THE SECOND LA W OF THERMODYNAMICS:ENERGY CONVERSION EFFICIENCIES
FORCED CONVECTION:GENERAL THERMAL ANALYSIS
NATURAL CONVECTION:EQUATION OF MOTION AND THE GRASHOF NUMBER

Leave a comment

Your email address will not be published. Required fields are marked *