Case studies:Variable speed drives on heating, ventilating, air conditioning {HVAC) system pumps.

Case study 4: Variable speed drives on heating, ventilating, air conditioning {HVAC) system pumps

Case study summary

Large energy savings were achieved by fitting VFDs on pumps previously allowed to run uncontrolled at their maximum flow, saving pumping cost and heating energy.

Other potential applications

Heating and air conditioning systems which see varying heating load, i.e. almost all of them.

Savings achieved

Installation and operation details

Variable frequency drives have been fitted on the pumps for chilled, hot and condenser water and also medium pressure water for the boiler room. The installation was at a large, international private bank in London. One 4 kW, one 22 kW and two 75 kW drives were retrofitted.

Sensors in the pipework, connected to the drives, regulate the speed of the pumps to ensure optimum usage of the water’s energy content. The system is coordinated with the building management system, enabling easy control of the indoor climate.

The pumps are now running at the speed needed by the process. This is generally about 40% of the maximum speed, at which the pumps previously ran continuously. Before fitting the VFDs, water would be pumped out at 40°C and return with no temperature drop. Now the return is 32°C. The overall energy saving in gas and electricity in this case is reported to be 90%. The lower pump speed is also reducing pump maintenance cost.

Related posts:

Case studies:VSD in a wastewater pumping scheme
Valves and Sensors:Proximity sensors
Gas–solid separation devices:Dust control and Particle degradation
ACTUATORS:Piston- Type Cylinders
Moisture and condensation:Relative humidity and Psychrometric chart.
Operating problems:Existing plant and Positive pressure systems
Review of pneumatic conveying systems:System types,Open systems and Positive pressure systems.
Introduction to pneumatic conveying and the guide:Definitions and Solids loading ratio
ACTUATORS:CONVERTING SCFM INTO COMPRESSOR HORSEPOWER
HYDRAULIC PUMPS:Centered Internal Gear
The flapper-nozzle.
Air Compressors, Air Treatment and Pressure Regulation
THE SECOND LA W OF THERMODYNAMICS:PERPETUAL-MOTION MACHINES
POWER AND REFRIGER A TION CYCLES:DEVIATION OF ACTUAL VAPOR POWER CYCLES FROM IDEALIZED ONES
SUMMARY OF HEAT EXCHANGERS

Leave a comment

Your email address will not be published. Required fields are marked *