The air relay and the force balance principle.

The air relay and the force balance principle

Air amplifiers balance input pressure and output pressure. An air relay, on the other hand (illustrated in Figure 7.5), balances input pressure with the force from a range spring. An increasing input signal causes air to pass from the supply to the load, while a decreasing input signal causes air to vent from the load. In the centre of the input signal range, there is no net flow to or from the output port.

Process control pneumatics-0192

An air relay is used to linearise a flapper-nozzle, as shown in Figure 7.6. Here, force from the unbalance in input pressures P1 and P2 is matched exactly by the force from the feedback bellows whose pressure is regulated by the air relay.

Suppose flow in the pipe increases, causing pressure difference P1-P2 to increase. Increased force from the bellows at the top decreases the flapper gap causing pressure at the air relay input to

Process control pneumatics-0193

rise. This causes air to pass to the feedback bellows, which apply a force opposite to that from the signal bellows.

The system balances when the input pressure from the flapper nozzle to the air relay (point A) is at the centre of its range at which point the air relay neither passes air nor vents the feedback bellows.

This corresponds to a fixed flapper-nozzle gap.

Figure 7.6 thus illustrates an example of a feedback system where the pressure in the feedback bellows is adjusted by the air relay to maintain a constant flapper-nozzle gap. The force from the feedback bellows thus matches the force from the input signal bellows, and output pressure is directly proportional to (P1-P2). The output pressure, driven directly from the air relay, can deliver a large air volume.

The arrangement in Figure 7.6 effectively operates with a fixed flapper-nozzle gap. This overcomes the inherent non-linearity of the flapper-nozzle. It is known as the force balance principle and is the basis of most pneumatic process control devices.

Related posts:

Control principles for variable speed pumping:Soft starting and stopping
Concepts for estimating pumping energy costs:Flow duration diagrams
System and process requirements:Introduction to variable speed concept
Health and safety:System components,Blowers ,compressors and Oil free air.
Erosive wear:Influence of variables and Theories proposed.
Hydraulic accessories:Flexible hoses.
COMPRESSORS:COMMON COMPONENTS
RESERVOIRS, STRAINERS, FILTERS, AND ACCUMULATORS:Proportional-Flow Filters
Control components in a hydraulic system:Flow control valves.
Sequencing applications.
Control Valves:types of control valve
Safety, Fault-Finding and Maintenance:safety
POWER AND REFRIGER A TION CYCLES: THE IDEAL CYCLE FOR SPARK-IGNITION ENGINES
HEAT EXCHANGERS:TYPES OF HEAT EXCHANGERS
NATURAL CONVECTION:EQUATION OF MOTION AND THE GRASHOF NUMBER

Leave a comment

Your email address will not be published. Required fields are marked *