Concepts for estimating pumping energy costs:Systems with static head

Systems with static head

In systems with static head (H5), the energy usage can be calculated in a slightly different way. The head needed from the pump can be separated into static and dynamic (friction losses). Substituting H5+Hr for the total head in the expression for specific energy will generate the following expressions:

VARIABLE SPEED PUMPING-0736

The “hydraulic system factor”, fHs. indicates the relative amount of static head in the system. It is obvious that Es now has a minimum value of H 8 x p x g which would occur if all efficiencies were equal to 100% (ry = 1) and there were no friction losses. If there is no variable speed drive in the system, then ‘YJdrive = 1. The different factors are all functions of the flow rate and will vary with the duty point. If a variable speed drive is used, they will vary with speed as the duty point moves along the system curve.

Motor efficiency will generally decrease as the speed is lowered and the motor goes below 75% of full load. The drop in combined motor- drive efficiency can be substantial if the motor load drops below 50% of full load. The denominator: ‘YJdrive x ‘Y/motor x ‘Y/pump x fHs can also be seen as the overall (gross) efficiency ‘Y/grĀ·

The hydraulic system factor will increase when the friction losses go towards zero, which happens when the duty point approaches the shut off head or when the friction losses are lowered. Hence lowering the friction losses has a substantial effect on the specific energy.

The specific energy will, however, always increase drastically as the duty point moves towards shut off head in systems with static head due to reduced pump, motor and drive efficiencies. In systems with high static head, this can happen even at a relatively moderate decrease in speed.

In such systems the area of usefulness of a variable speed drive can be somewhat improved by making sure that the system curve and the full speed pump curve intersect to the right of the pump’s best efficiency point.

To calculate the cost of pumping, the specific energy has to be calculated at all operating points along the system curve. By combining this information with the information in the flow duration diagram the cost of pumping can be determined.

Related posts:

Valves and Sensors:Control valves
Health and safety:Explosion protection
Low pressure and vacuum:Pressure drop and Maintenance
Introduction to pneumatic conveying and the guide:Information provided ,Availability of design data ...
Design procedures:The use of equations in system design and Logic diagram for system design.
FORCES IN LIQUIDS:STREAMLINE AND TURBULENT FLOW.
Hydraulic accessories:Filters and strainers
LINES, FITTINGS, AND SEALS:TYPES OF FITTINGS AND CONNECTORS
Pneumatic controllers.
Fundamental Principles:Fundamental Principles
Safety, Fault-Finding and Maintenance:cleanliness
INTRODUCTION TO THERMAL-FLUID SCIENCES
GAS MIXTURES AND PSYCHROMETRICS:COMPOSITION OF A GAS MIXTURE: MASS AND MOLE FRACTIONS
HEAT EXCHANGERS:THE OVERALL HEAT TRANSFER COEFFICIENT
NATURAL CONVECTION:NATURAL CONVECTION FROM FINNED SURFACES AND PCBs

Leave a comment

Your email address will not be published. Required fields are marked *