The flapper-nozzle.

The flapper-nozzle

Most properties (eg flow, pressure, level, error, desired valve position) can be converted to a small movement. The heart of all pneu­matic process control devices is a device to convert a small displacement into a pressure change, which represents the property causing the displacement. This is invariably based on the flapper­ nozzle, whose arrangement, characteristic and application are illus­trated in Figure 7.3.

An air supply (typically, 2 to 4 bar) is applied to a very fine nozzle via a restriction as shown in Figure 7.3a. The signal output side of the nozzle feeds to a closed (non-venting) load, such as an indicator. Air escapes as a fine jet from the nozzle, so the pressure at A is lower than the supply pressure because of the pressure drop across the restriction.

Process control pneumatics-0190

Air loss from the jet (and hence pressure at A) is influenced by the gap x between the nozzle and movable flapper; the smaller the gap, the lower the air flow and higher the pressure. A typical response is shown in Figure 7.3b, illustrating the very small range of displacement and the overall non-linear response. The response can, however, be considered linear over a limited range (as shown) and the flapper-nozzle is generally linearised by use of a force balance system as described later.

Figure 7.3c shows a very simple differential pressure transducer which may be used as a flow transmitter by measuring the pressure drops across an orifice plate. The difference in pressure between P1 and P2 causes a force on the flapper. Assuming P1>P2 (which is true for the direction of flow shown), the top of the flapper is pushed to

the right until the force from (P1-P2) is matched by the force from the spring extension. Flapper nozzle gap, and hence the output pressure, is thus determined by the differential pressure and the flow through the orifice plate.

The arrangement of Figure 7.3c is non-linear, and incapable of maintaining output pressure to a load with even a small loss of air. Even with a totally sealed load the minimal air flow through the restriction leads to a first order lag response with a very long time constant. A flapper-nozzle is therefore usually combined with an air amplifier, or volume booster, which takes a pressure as the input and gives a linearly-related pressure output – with an ability to supply a large volume of air. When combined with the force balance principle described later, the inherent non-linearity of the flapper nozzle can be overcome.

Incoming search terms:

Related posts:

Benefits, drawbacks and operational issues:Operating motors above base speed
Compressed Air Transmission and Treatment:Carbon monoxide
Pipelines and valves:Isolating valves and Butterfly valves
THE COMPRESSOR:COMPRESSOR NOISE REDUCTION
Introduction to pneumatic conveying and the guide:Information provided ,Availability of design data ...
COMPRESSORS:ROTARY COMPRESSORS
Hydraulic fluids:Fire-resistant fluids
Hydraulic circuit design and analysis:Symbols of hydraulic components
Fault-finding instruments.
Pneumatic piping, hoses and connections.
Process Control Pneumatics:signals and standards
INTRODUCTION AND OVERVIE:MATHEMATICAL MODELING OF ENGINEERING PROBLEMS
BASICCONCEPTS OF THE RMODYNAMICS:CLOSED AND OPEN SYSTEMS
ENERGY TRANSFER BY HEAT,WORK,AND MASS:FLOW WORK AND THE ENERGY OF A FLOWING FLUID
THE SECOND LA W OF THERMODYNAMICS:THE CARNOT CYCLE

Leave a comment