Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
INDUCTION MACHINE TRANSIENTS
The Triac
Light and associated radiation:Nature of light
Basic Concepts of Static Control
Objective tests on transformer
Electric Motor Manual – SELECTION AND APPLICATION – Reducing motor losses
Electric Motor Manual – SELECTION AND APPLICATION – Effect of motor efficiency on energy...
Motor Installation:Determining Motor Current
UNBALANCED SUPPLY VOLTAGES
Light and associated radiation:Photoresistors and photoconductors
Single-phase motors:Repulsion Induction Motor
Audio Principles:Frequency Discrimination
REAL-TIME OPERATING SYSTEMS:SEMAPHORES
Other Digital Audio Devices:WAV Onward