Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
The Essentials of Computer Organization and Architecture - Historical Development
Start-Stop Push-Button Control
summary Of Inductance
NETWORKING WIRED AND WIRELESS:ISM-BAND RADIOS
Alternators:Effect of Harmonics on Pitch and Distribution Factors
Sound, infrasound and ultrasound:Electrical to audio transducers
Hazardous Materials:Disposing Of hazardous Materials
CONVENTIONAL D.C. MOTORS:TOY MOTORS
Valve (Tube-Based) Amplifiers:Effect of Output Load Impedance
The Essentials of Computer Organization and Architecture - Boolean Algebra and Digital Logic
Manual starters:Manual Push-Button Starters
Signal-carrying switches:Special requirements
INTRODUCTION TO SYNCHRONOUS, BRUSHLESS D.C. AND SWITCHED RELUCTANCE DRIVES
Certification for the Electricity and Electronics Field:Basis for Certification