Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
Speed control of d.c. Motors:Series Motor Starters
SUMMARY of inducation machiens
Preamplifiers and Input Signals:Performance Standards
Three-phase Distribution Boards And Socket Circuits:Three-Phase Distribution Board
Amplifier Applications:Direct-coupled Amplifiers
RADIO/WIRELESS:RADIO HARDWARE
Electric Motor Manual – INSTALLATION METHODS - Troubleshooting motor capacitors
Power and Energy:Measuring Power and Energy
Solids, liquids and gases:Gases
Input Devices
ELECTRIC CONTROL FUNDAMENTALS
Single-phase motors:Hysteresis Motor
Monitoring Systems part1
Headphones:A Brief History