Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
LOSSES AND EFFICIENCY OF DC MACHINES
Compact Disc:Problems with Digital Encoding
Integrated Circuits:Integrated circuit Packaging
Programming A Plc:Entering the Program
The Essential Guide to Semiconductors – Essential Guide to Custom and Configurable Chips
Digital Audio Production:Hard Drive Interface Standards
Digital Logic
POWER ELECTRONIC CONVERTERS FOR MOTOR DRIVES:VOLTAGE CONTROL – D.C. OUTPUT FROM D.C. SUPPLY
Troubleshooting:Voltmeter Basics
ELECTRIC CONTROL FUNDAMENTALS:SERIES 60 TWO-POSITION CONTROL CIRCUITS
Analog Sensing for Programmable Controllers
Power and Energy:Power in a Parallel Circuit
INTRODUCTION TO MACHINERY PRINCIPLES:MAGNETIC BEHAVIOR OF FERROMAGNETIC MATERIALS
Other sensing methods:Permeability and magnetic measurements