Fixed Appliance and Socket Circuits:Continuity of Ring Circuit Conductors

Continuity of Ring Circuit Conductors

( Stage One )

A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.

The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.

Fixed Appliance and Socket Circuits-0857

Readings 1 and 2 should be the same

Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.

Incoming search terms:

Leave a comment

Your email address will not be published. Required fields are marked *