Testing and Commissioning of Protective Relays and Instrument Transformers:Maintenance and Testing of Instrument Transformers

Maintenance and Testing of Instrument Transformers

The following general recommendations are offered to supplement the manufacturer ’s instructions.

General maintenance

• If instrument transformers are allowed to remain out of service for a long period of time, they should be dried before being put into service

• Instrument transformers containing oil or synthetic dielectrics should be tested periodically to determine the breakdown voltage remains at 26 kV or above

• The secondaries of CTs that are not connected to relays, meters, and the like, should have their secondaries shorted and grounded as mentioned in Section 9.2.8

• The secondary circuits and cases of all instrument transformers should be grounded with at least a number 12 AWG conductor as discussed earlier in Section 9.2.8

Testing

Routine testing as described below should be performed on instrument transformers.

General purpose instrument transformers

• Ratio and phase angle tests should be made on CTs for metering at 100% and 10% of rated primary current, when energized at rated frequency with maximum standard burden for which the transformer is rated

• The turns ratio and polarity tests should be made on CTs for relaying to ensure that they have the correct turns ratio and relaying accuracy

Revenue metering instrument transformer

• Calibrate all meters at 10%, 50%, and 90% of full scale. Instruments used for calibration of test equipment should have precision of no more than 50% of the instrument being tested.

• Calibrate watt-hour meters to 0.5%.

• Verify all instrument multipliers.

Leave a comment

Your email address will not be published. Required fields are marked *