Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
CONTROL FUNDAMENTALS:COOLING EQUIPMENT
Troubleshooting variable speed drives:Single-phase pulse width modulation (PWM) inverter
Basic troubleshooting principles:Testing devices
GENERATOR COMPONENTS, AUXILIARIES, AND EXCITATION:SHAFT SEALS AND SEAL OIL SYSTEMS
SUBSYNCHRONOUS RESONANCE (SSR)
Fuel System – Carburetor Service (part5)
Troubleshooting the Two-Speed One-Winding Motor
bipolar Transistors:Transistor Construction
Loudspeakers:Electrical Analogue
Electric Motor Manual – SELECTION AND APPLICATION – Selecting brushes for motors and gen...
Basic troubleshooting principles:Checks for circuit continuity with disconnected supply
How Engines Work part3
POLYPHASE MACHINES
summary of current