Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
CIRCUIT BREAKERS:RECENT DEVELOPMENTS IN CIRCUIT BREAKERS
Synchronous Motor:Effect of Changing Excitation on Constant Load
Electrical System part1
Special machines:AC Servo motors
Fundamentals of Electricity:resistance
Developing Control Circuits:Developing Control Circuits
Amperes and Rotor Bar Design
Interfacing and Processing:LED + LDRs
PROGRAMMABLE-LOGIC AND APPLICATION-SPECIFIC INTEGRATED CIRCUITS (PLASIC):PERIPHERAL PROGRAMMABLE-LOG...
VARIABLE-SPEED DRIVES:AC DRIVE APPLICATION ISSUES
Split-Phase Motors
Review of Field Testing the DC Machine
Timing relays:Clock Timers
Proximity detectors:Ultrasonic Proximity Detectors