Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
Data Compression:Lossless Compression
CONTROL FUNDAMENTALS:HVAC SYSTEM CHARACTERISTICS
CIRCUIT BREAKERS:THEORY OF CIRCUIT INTERRUPTION AND PHYSICS OF ARC PHENOMENA
CONTROL FUNDAMENTALS:TIMED TWO-POSITION CONTROL
Schematics and Wiring Digrams
Position, direction, distance and motion:Direction
Acoustic Environment:Temperature-Dependent Velocity
Valve (Tube-Based) Amplifiers:Output (Load-Matching) Transformer
INSTALLING CONTROL SYSTEMS
Other Digital Audio Devices:MPEG Systems
Electric Motor Manual – INSTALLATION METHODS - Nameplate data-for better motor installation an...
Multicore Cables and Cabletray:Power Loss in Cables
Electrolytic Capacitor Components
Introduction to AC:AC Waveform Values