Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
Introduction to Three-Phase Motor Types
Pressure Switches and Regulators
Troubleshooting variable speed drives:Precautions for start/stop control of AC drives
GENERAL PRINCIPLES OF MOTOR CONTROL:Installation of Motors and Control Equipment
Speed control of d.c. Motors:Thyristor Speed Control of Separately-excited D.C. Motor
Lamps and Light Fittings:Tungsten Halogen Lamps
Capacitor Test Formula
Engine Valve System part8
Engine Valve System part9
RUNNIG OVERCURRENT PROTECTION
ELECTRIC MOTORS:SPECIFIC LOADINGS AND SPECIFIC OUTPUT
Introduction to Room Acoustics
AUDIO AND VIDEO SYSTEMS – VIDEO TAPE RECORDING AND REPRODUCTION
MICROPROCESSORS:MULTICORE MICROPROCESSOR UNITS