Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
GENERATOR COMPONENTS, AUXILIARIES, AND EXCITATION:SHAFT SEALS AND SEAL OIL SYSTEMS
Relayes And Contactors
TRANSFORMER COMPONENTS AND MAINTENANCE:FORCES AND CAUSE OF TRANSFORMER FAILURES
FUNDAMENTALS OF ELECTRIC SYSTEMS:CAPACITORS
MAINTENANCE OF MOTORS:ENCLOSURES AND COOLING METHODS
PNEUMATIC CONTROL FUNDAMENTALS:THROTTLING RANGE ADJUSTMENT
Analog Sensing for Programmable Controllers
Power Supply Design:Half-Wave and Full-Wave Rectification
P–N Junction Diodes:Diode Biasing
Digital Logic:The OR Gate and The INVERTER
CELL PHONES:A LOOK INSIDE A 3G CELL PHONE
INDUCTION MOTOR EQUIVALENT CIRCUIT:PROPERTIES OF INDUCTION MOTORS
DC Circuits:Wheatstone Bridge
Capacitance:capacitors