Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
Model validation on no-load
THE OUTPUT COEFFICIENT DESIGN CONCEPT
Digital Logic:Integrated Circuits
GENERATOR COMPONENTS, AUXILIARIES, AND EXCITATION:STATOR WINDING WATER COOLING SYSTEMS
BASIC POLE-CHANGING THREE-PHASE A.C. WINDINGS
VIBRATION ANALYSIS:VIBRATION SEVERITY
D.c. Motor:Motor Principle
Interfacing and Processing:Subsonic Protection and High-Pass Filtering
CONTROL FUNDAMENTALS:COOLING EQUIPMENT
Troubleshooting AC motors and starters:Motor testing
Cables and Cable Termination:Role of Electrical Bodies
Audio Amplifier Performance:AC- and DC-Coupled Amplifiers
Instrumentation techniques:Op-amps
GENERATOR MAIN CONNECTIONS