Continuity of Ring Circuit Conductors
( Stage One )
A ring circuit continuity test must be done to ensure that each phase, neutral and protective conductor is continuous and not broken at any point. If any conductor were broken then the load would not be properly shared by the conductors, possibly leaving one conductor overloaded and not adequately protected.
The ring circuit continuity test may be carried out as shown in Figure 22. The six conductors are disconnected from their respective terminals and the continuity of each of the three “rings” is checked in turn.
Readings 1 and 2 should be the same
Example 0.3 Ohms, the resistance of 43 metres of 2.5 mm2 cable.
The relationship between the resistance of 2.5 mm2 cable and 1.5 mm2 cable is 1.67. Reading 3 should be higher by a factor of 1.67.
Example 0.3 x 1.67 = 0.5 Ohms, resistance of 43 metres of 1.5 mm2 cable.
Related posts:
Operation of the DC Welder Generator
Starting the Motor After the Comparison Test from Control
Binary number System:Binary And decimal conversion
Electrical or Mechanical Interlock and Sequence Control
State Variable Feedback Control Theory:State Variable Feedback Control Theory
Relayes And Contactors
Zener Diodes:testing Zener Diodes
CONTROL FUNDAMENTALS:DEFINITIONS
Float Switch Control of a Pump and Pilot Lights (Circuit #3)
The Triac Used for AC Voltage Control
THE BASIC MAGNETIZATION CURVE
Troubleshooting and Repairing Computer Printers – Troubleshooting guidelines
DC Circuits:Series-Parallel Circuits
Introduction in Basic troubleshooting principles