Wye/Delta or Y/∆ Connection
The main use of this connection is at the substation end of the transmission line where the voltage is to be stepped down. The primary winding is Y-connected with grounded neutral as shown in Fig. 33.6. The ratio between the secondary and primary line voltage is 1/ 3 times the transformation ratio of each trans- former. There is a 30° shift between the primary and secondary line voltages which means that a Y – D transformer bank cannot be paralleled with either a Y – Y or a D – D bank. Also, third harmonic currents flows in the D to provide a sinusoidal flux.
Delta/Wye or ∆/Y Connection
This connection is generally employed where it is necessary to step up the voltage as for example, at the beginning of high tension transmission system. The connection is shown in Fig. 33.7. The neutral of the secondary is grounded for providing 3-phase 4-wire service. In recent years, this connection has gained considerable popularity because it can be used to serve both the 3-phase power equipment and single-phase lighting circuits.
This connection is not open to the objection of a floating neutral and voltage distortion because the existence of a D-connection allows a path for the third-harmonic currents. It would be observed that the primary and secondary line voltages and line currents are out of phase with each other by 30°. Because of this 30° shift, it is impossible to parallel such a bank with a D – D or Y – Y bank of transformers even though the voltage ratios are correctly adjusted. The ratio of secondary to primary voltage is 3 times the transformation ratio of each transformer.
Example 33.1. A 3-phase, 50-Hz transformer has a delta-connected primary and star-connected secondary, the line voltages being 22,000 V and 400 V respectively. The secondary has a star- connected balanced load at 0.8 power factor lagging. The line current on the primary side is 5 A. Determine the current in each coil of the primary and in each secondary line. What is the output of the transformer in kW ?
Solution. It should be noted that in three-phase transformers, the phase transformation ratio is equal to the turn ratio but the terminal or line voltages depend upon the method of connection employed. The D/Y connection is shown in Fig. 33.8.
Example 33.6. A 100-kVA, 3-phase, 50-Hz 3,300/400 V transformer is D-connected on the h.v. side and Y-connected on the l.v. side. The resistance of the h.v. winding is 3.5 W per phase and that of the l.v. winding 0.02 W per phase. Calculate the iron losses of the transformer at normal voltage and frequency if its full-load efficiency be 95.8% at 0.8 p.f. (lag).
(A.C. Machines-I, Jadavpur Univ. 1989)
Example 33.8. A 3-phase transformer has its primary connected in D and its secondary in Y. It has an equivalent resistance of 1% and an equivalent reactance of 6%. The primary applied voltage is 6,600 V. What must be the ratio of transformation in order that it will deliver 4,800 V at full-load current and 0.8 power factor (lag) ?
(Elect. Technology-II, Magadh Univ. 1991)
Tutorial Problem No. 33.1
1. A 3-phase, star-connected alternator generates 6,360 V per phase and supplies 500 kW at a p.f. 0.9 lagging to a load through a step-down transformer of turns 40 : 1. The transformer is delta connected on the primary side and star-connected on the secondary side. Calculate the value of the line volts at the load. Calculate also the currents in (a) alternator windings (b) transformer primary windings (c) transformen secondary windings.
[476 V (a) 29.1 A (b) 16.8 A (c) 672 A]
2. A 11,000/6,600 V, 3-f, transformer has a star-connected primary and a delta-connected secondary. It supplies a 6.6 kV motor having a star-connected stator, developing 969.8 kW at a power factor of 0.9 lagging and an efficiency of 92 per cent. Calculate (i) motor line and phase currents (ii) transformer secondary current and (iii) transformer primary current.
[(a) Motor ; IL = Iph = 126.3 A (b) phase current 73 A (c) 75.8 A]
Related posts:
Incoming search terms:
- 86 OR CHINA Transformer\ @126 com mail
- VS DELT YY TRANSFORMERS
- current transfomer ratios calculation on star delta transformer
- delta wye transformer phase shift power factor correction
- delta wye transformer calculations
- convert 100 kva to kw 3 phase#imgrc=WLgminkxjJGKkM:
- 3phase 50Hz transformer deleta connected the linevolte being 22000v
- what are the factors that determine the transformation ratio of a three phase transformer
- solution to A thrre phase 415V load takes a line current of 800A from a 3300/415V delta-star transformer
- equivalent tranformer wye delta of 3
- what is the winding connection that will b suitable for a 15MVA/11KV 50Hz three phase transformer
- what are the factors that determine the transformation ratio of a three—phase transformer?
- a transformer bank of 7 967KV/230V each are connected in wye-delta connection supply a three phase load of 100kVa
- the turns ratio of a 11000/415 V Delta/Star connected 3phase transformer is ------------
- 3 star connected aditical coils are suppyed by 200V 3Phase suppy each coil are take 1000W the power facter is O Point 8 lagging what are the line current If total power of coils are in delta connection Ans
- 3 single phase loads each of Kw and having a powerfactor of lagging are connected in delta to the star connected secondary of transformer the secondary phase voltage of transformer is 6 6kv calculate the voltage across eachload and the current in each loa
- factors determining traformer ratio in three phase transformer
- factors that determine the transformation ratio of a three—phase transformer?
- 15mva 33/11kv winding connection
- observation the phase shift in delta wye transformer in 3 phase transmission line
- electrical 3phase transformer connection arts name
- do we use phase or line values to calculate transformation ratio in 3 phase
- describe the winding connection suitable for a 15mvA 33/11kv 3-phase transformer
- calculate ratios on the hv side and lv side of transformer
- delta wye transformer vendor for machinery
- consider 11KV/400v step down distribution transform delivers 200KVA balanced load and 120KW active power calculat reactlv power and power facter?
- delta wye transformer in 3 phase transmission line
- calculate voltage ratio of a three phase delta star connected transformer that delivers a line voltage of 346 41 V when connected to a 6kV supply
- delta wye primary and secondary voltage calculations
- delt delta star transformer
- 400v ac connection to a 11kv transformer
- A three - phase 415V load takes a line current of 800A from a 3300/415V delta-star transformer The 3300V system is supplied from an 11000/3300V star- star transformer a ) Draw the network diagram and assuming no losses find both line and phase values of v
- 3 phase y-delta
- 3 phase delta star transformer efficiency
- 3 phase 415v delta connected full load current is
- 3 pahse star Delta transformer and solution
- 3 - 10 kva 1330/230v 50Hz transformers are connected in star delta to supply a 230V line to line heating load of 2 kW per phase and 3 phase induction motor load of 21kVA The power factor of induction motor load is 0 8 Determine the line current supplying
- 11kV transformer has line or phase voltage
- 11kv to 415v transformer
- 11000/433 v transformer line voltage determine
- wye wye conncetion windings observation
- 50kw 440v 3 phase across motor efficiency 90% 0 8 lagging power factor supplied by 6600/440v delta star currents calculate
- a 50kw 440v phase ac motor has an efficiency of 90% and operates at 0 8 lagging power when on full load it is supplied by a 6600/440v delta star
- a 50 hp 440v three phase induction motor with an efficiency of 9 and power factor 85 an full load is supplied from 6600/440v delta to star connected transformer ignoring exciting current calculate current in low and high voltage winding of transformer whe
- A 400 V 3-phase star connected alternator supplie
- a 3-phase ac motor has efficiency of 90% power factor 0 8 delta-star transformer calculate phase currents
- a 3 phase transformer has its primary connected in delta and secondary connected in star secondary to primary turns ratio per phase is 5 what would be the secondary voltage for a primary voltage of 400v
- a 3 phase star connected alternator generates 6360 v per phase and supplies 500kw
- a 3 phase delta star transformer is supplied at 6000 v on the delta connected side the terminal voltage on the secondary side when supplying full load at 0 8 lagging power factor is 415 v the equivalent resistance and reactance drops for the transformer a
- a 3 phase 33000/6600 v