Other system components:Solenoid valve

This chapter describes the function and operation of a number of components not previously covered in detail.

Solenoid valve

This is an electrically operated magnetic valve. It consists of a coil wound around a sleeve of non-magnetic substance. When energized, the coil carries an electrical current and becomes a magnet.

Inside the sleeve is a movable iron core, which will be attracted by the magnetic field of force to remain suspended in a midway position inside the sleeve. The iron core movement opens the valve. When the coil is de-energized, the iron core returns to its normal position to close the valve.

This type is normally closed. Others are available which are normally open; these close when the coil is energized.

Some solenoid valves have flare fitting unions, whilst others are brazed into position. It is important that the coil is removed when brazed joints are made. For optimum operation the valve should be installed in an upright position and rigidly mounted; the valve should never rely on the system pipework for support.

There are many uses for this type of valve, such as in defrost systems, multiple evaporator systems and pump-down cycles. In effect, it is used wherever it is necessary to stop the flow of refrigerant to a specific section of pipework on a particular application.

Crankcase heater

This is a resistance heater. If externally mounted it is located on the underside of the compressor crankcase. It may be mounted internally as an integral part of the compressor; this is standard for larger commercial equipment.

The presence of liquid refrigerant in a compressor crankcase is wholly undesirable. It could cause dilution of the lubricating oil, resulting in poor lubrication. Liquid refrigerant vaporizing in a crankcase will cause foaming when the compressor operates after an off cycle. Excess oil will then be discharged by the compressor; this could drastically reduce the amount of oil in the crankcase. Non-condensible slugs of oil and liquid refrigerant could enter the compressor cylinders to cause considerable damage to valves, pistons and connecting rods, and even to fracture crankshafts.

Crankcase heaters are essential for compressors installed for low temperature applications, where evaporating temperatures and crankcase temperatures can be extremely low. They are also necessary for remote installations where the compressor is exposed to low ambient temperatures (winter conditions). Whenever the crankcase temperature falls below that of the evaporator, refrigerant vapour will migrate and condense in the crankcase unless a heater is employed to maintain a temperature in the crankcase above the temperature of the refrigerant vapour.

Because of the tendency of oil to absorb miscible refrigerant, a certain amount of refrigerant will always be present in the crankcase.