HEATING CIRCUITS:MANUFACTURER’S DIAGRAMS

MANUFACTURER’S DIAGRAMS

Figure 13.4 shows how the manufacturer represents the location of the various furnace devices. The solid lines indicate the line voltage to be installed. The dotted lines are the low voltage to be installed when the furnace is put into service.

The motor is four speed. It has various colored leads to represent the speeds. You may have to change the speed of the motor to move the air to a given location. Most motors come from the factory with a medium-high speed selected. The speed is usually easily changed by removing a lead from one point and placing it on another where the proper color is located. In the schematic shown in Figure 13.5, the fan mo- tor has a white lead connected to one side of the 120-volt line (neutral), and the red and black leads are switched by the indoor blower relay to black for the cooling speed and red for the heating speed. It takes a faster fan motor to push cold air than hot air because cold air is heavier.

HVAC LICENSING EXAM STUDY GUIDE-0147

In Figure 13.5, the contacts on the thermostat are labeled R, W, Y, G, R, and W. They are used to place the thermostat in the circuit. It can be switched from W to Y manually by moving the heat-cool switch on the thermostat to the cool position.

Notice in Figure 13.5 that the indoor blower-relay coil is in the circuit all the time when the auto-on switch on the thermostat is located at the on position. The schematic also shows that the cool position has been se- lected manually, and the thermostat contacts will complete the circuit when it moves from W1 to Y1.

In Figure 13.4, note that the low-voltage terminal strip has a T on it. This is the common side of the low voltage from the transformer. In Figure 13.5, the T is the common side of the low-voltage transformer secondary. In Figure 13.4, the T terminal is connected to the compressor contactor by a wire run from the terminal to the contactor. Note that the other wire to the contactor runs from Y on the terminal strip. Now go back to Figure 13.5, where the Y and T terminals are shown as connection points for the compressor con-

HVAC LICENSING EXAM STUDY GUIDE-0148

tactor. Are you able to relate the schematic to the actual device? The gas valve is wired by attaching wire T of the terminal strip to one side of the solenoid and running a wire from the limit switch to the other side of the solenoid.

Figure 13.6 shows how the wiring diagram comes from the factory. It is usually located inside the cover for the cold-air return. In most instances it is glued to the cover so that it is handy for the person working on the furnace whenever there is a problem after installation.