In this chapter, a digital circuit will be designed to per- form the same function as a common relay circuit. The relay circuit is a basic stop-start, push-button circuit with overload protection (Figure 52 – 1).
Before beginning the design of an electronic circuit that will perform the same function as this relay circuit, the operation of the relay circuit should first be dis- cussed. In the circuit shown in Figure 52 – 1, no current can flow to relay coil M because the normally open START button and the normally open contact are con- trolled by relay coil M.
When the START button is pushed, current flows through the relay coil and normally closed overload con- tact to the power source (Figure 52 – 2). When current flows through relay coil M, the contacts connected parallel to the START button close. These contacts maintain the circuit to coil M when the START button re- leases and returns to its open position (Figure 52 – 3).
The circuit will continue to operate until the STOP button is pushed and breaks the circuit to the coil (Figure 52– 4). When the current flow to the coil stops, the relay de-energizes and contact M reopens. Since the START button is now open and contact M is open, there is no complete circuit to the relay coil when the STOP button is returned to its normally closed posi- tion. If the relay is to be restarted, the START button must be pushed again to provide a complete circuit to the relay coil.
The only other logic condition that can occur in this circuit is caused by the motor connected to the load contacts of relay M. Assume the motor is con- nected in series with the heater of an overload relay
If the motor is overloaded, it will cause too much current to flow through the circuit. When a current greater than normal flows through the overload heater, the heater produces more heat than it does under nor- mal conditions. If the current becomes high enough, it will cause the normally closed overload contact to open.
Notice that the overload contact is electrically isolated from the heater. The contact, therefore, can be connected to a different voltage source than the motor.
If the overload contact opens, the control circuit is broken and the relay de-energizes as if the STOP button had been pushed. After the overload contact has been re- set to its normally closed position, the coil will remain de-energized until the START button is again pressed.
Now that the logic of the circuit is understood, a digital logic circuit that will operate in this manner can be designed. The first problem is to find a circuit that can be turned on with one push button and turned off with another. The circuit shown in Figure 52 – 7 can per- form this function. This circuit consists of an OR gate
and an AND gate. Input A of the OR gate is connected to a normally open push button, which is connected to 5 volts DC. Input B of the OR gate is connected to the output of the AND gate. The output of the OR gate is connected to input A of the AND gate. Input B of the AND gate is connected through a normally closed push button to +5 volts DC. This normally closed push but- ton is used as the STOP button. The output of the AND gate is the output of the circuit.
To understand the logic of this circuit, assume that the output of the AND gate is low. This produces a low at input B of the OR gate. Since the push button connected to input A is open, a low is produced at this input also. When all inputs of an OR gate are low, its output is also low. The low output of the OR gate is connected to input A of the AND gate. Input B of the AND gate is connected to a high through the normally closed push- button switch. Since input A of the AND gate is low, the output of the AND gate is forced to remain in a low state.
When the START button is pushed, a high is connected to input A of the OR gate. This causes the out- put of the OR gate to change to high. This high output is connected to input A of the AND gate. The AND gate now has both of its inputs high, so its output changes from a low to a high state. When the output of the AND gate changes to a high state, input B of the OR gate becomes high also. Since the OR gate now has a high connected to its B input, its output will remain high when the push button is returned to its open condition and input A becomes low. Notice that this circuit operates the same as the relay circuit when the START button is pushed. The output changes from a low state to a high state and the circuit locks in this condition so the START button can be reopened.
When the normally closed STOP button is pushed, input B of the AND gate changes from high to low. When input B changes to a low state, the output of the AND gate changes to a low state also. This causes a low to appear at input B of the OR gate. The OR gate now has both of its inputs low, so its output changes from a high state to a low state. Since input A of the AND gate is now low, the output is forced to remain low when the STOP button returns to its closed position and input B becomes high. The circuit designed here can be turned on with the START button and turned off with the STOP button.
The next design task is to connect the overload con- tact to the circuit. The overload contact must be connected in such a manner that it will cause the output of the circuit to turn off if it opens. One’s first impulse might be to connect the overload contact to the circuit as shown in Figure 52 – 8. In this circuit, the output of AND gate #1 has been connected to input A of AND gate #2. Input B of AND gate #2 has been connected to a high through the normally closed overload contact. If the overload contact remains closed, input B will remain
high. The output of AND gate #2 is, therefore, controlled by input A. If the output of AND gate #1 changes to a high state, the output of AND gate #2 will also change to a high state. If the output of AND gate #1 becomes low, the output of AND gate #2 will become low also.
If the output of AND gate #2 is high and the over- load contact opens, input B will become low and the output will change from a high to a low state. This cir- cuit appears to operate with the same logic as the relay circuit until the logic is examined closely. Assume that the overload contacts are closed and the output of AND gate #1 is high. Since both inputs of AND gate #2 are high, the output is also high. Now assume that the over- load contact opens and causes input B to change to a low condition. This forces the output of AND gate #2 to change to low state also. Input A of AND gate #2 is still high, however. If the overload contact is reset, the output will immediately change back to a high state. If the overload contact opens and is then reset in the relay circuit, the relay will not restart itself. The START but- ton must be pushed to restart the circuit. Although this is a small difference in circuit logic, it could become a safety hazard in some cases.
This fault can be corrected with a slight design change. Refer to Figure 52 – 9. In this circuit, the normally closed STOP button has been connected to input A of AND gate #2, and the normally closed overload switch has been connected to input B. As long as both of these inputs are high, the output of AND gate #2 will provide a high to input B of AND gate #1. If either the STOP button or the overload contact opens, the output of AND gate #2 will change to a low state. When input B of AND gate #2 changes to a low state, it will cause the output of AND gate #1 to change to a low state and unlock the circuit, just as pushing the STOP button did in the circuit shown in Figure 52 – 8. The logic of this digital circuit is now the same as the relay circuit.
Although the logic of this circuit is now correct, there are still some problems that must be corrected. When gates are used, their inputs must be connected to a definite high or low. When the START button is in its normal position, input A of the OR gate is not connected to anything. When an input is left in this condition, the gate may not be able to determine if the input should be high or low. The gate could, therefore, assume either condition. To prevent this, inputs must always be connected to a definite high or low.
When using TTL logic, inputs are always pulled high with a resistor as opposed to being pulled low. If a resistor is used to pull an input low as shown in Figure 52 – 10, it will cause the gate to have a voltage drop at its output. This means that in the high state, the output of the gate may be only 3 or 4 volts instead of 5 volts. If this output is used as the input of another gate, and the other gate has been pulled low with a resistor, the output of the second gate may be only 2 or 3 volts. No- tice that each time a gate is pulled through a resistor, its outcome voltage becomes low. It this were done through
several steps, the output voltage would soon become so low it could not be used to drive the input of another gate.
Figure 52 – 11 shows a resistor used to pull the in- put of a gate high. In this circuit, the push button is used to connect the input of the gate to ground, or low.
The push button can be adapted to produce a high at the input instead of a low by adding an INVERTER as shown in Figure 52 – 12. In this circuit, a pull-up resistor is connected to the input of an INVERTER. Since the input of the INVERTER is high, its output
will produce a low at input A of the OR gate. When the normally open push button is pressed, a low will be produced at the input of the INVERTER. When the input of the INVERTER becomes low, its output becomes high. Notice that the push button will now produce a high input A of the OR gate when it is pushed.
Since both of the push buttons and the normally closed overload contact are used to provide high in- puts, the circuit is changed as shown in Figure 52 – 13. Notice that the normally closed push button and the normally closed overload switch connected to the in- puts of AND gate #2 are connected to ground instead of Vcc. When the switches are connected to ground, a low is provided to the input of the INVERTERS to which they are connected. The INVERTERS, there- fore, produce a high at the input of the AND gate. If one of these normally closed switches opens, a high will be provided to the input of the INVERTER. This will cause the output of the INVERTER to become low. If the logic of the circuit shown in Figure 52 – 13 is checked, it can be seen that it is the same as the logic of the circuit shown in Figure 52 – 9.
The final design problem for this circuit concerns the output. So far, a light-emitting diode has been used as the load. The LED is used to indicate when the output is high and when it is low. The original circuit, however, was used to control a 120 volt AC motor. This control can be accomplished by connecting a solid- state relay to the output in place of the LED (Fig- ure 52 – 14). In this circuit, the output of AND gate #1 is connected to the input of an opto-isolated, solid-state relay. When the output of the AND gate changes to a high condition, the solid-state relay turns on and connects the 120 volt AC load to the line.
Review Questions
1. In a relay circuit, what function is served by the holding contacts?
2. What is the function of the overload relay in a motor control circuit?
3. What conditions of input must exist if an OR gate is to produce a high output?
4. What conditions of input must exist if an AND gate is to produce a high output?
5. When connecting TTL logic, why are inputs pulled high instead of low?
6. Referring to Figure 52 – 9, how would this circuit operate if input B of the OR gate was reconnected to input A of AND gate #1 instead of its output?
7. Referring to Figure 52 – 12, what function does the INVERTER serve in this circuit?
Related posts:
Incoming search terms:
- start stop circuit with relay
- start stop circuit digital circuit
- Start and stop push button
- single push button start stop logic
- start stop push button
- push button to start a motor dc
- specs for start stop buttons
- Equipment stop button
- start stop just using start button
- start stop retain control circuits
- explain why stop button must be normally close and a start button must be normally open
- features and applications of electrical machines stop/start/retain
- forces motors to start or stop in a predetermined order
- diagarm stope buyyons
- what is the purpose of the stop on motors
- OL? in stop start push button
- purpose and operatuion of stop motor
- push button start stop
- how to wire a stop start button
- why is the stop button more larger than the start button in the machine
- start/stop gate
- one push button start stop circuit diagram
- electric motor start stop circuit
- start stop motor with one push button
- electrical stop start circiuts with safety
- stop button
- start stop retain relay circuit explanied
- stop start retain relay control circuit
- electric controller stop button
- describe the operation and use of a stop/start/retain relay control circuit for an ac or dc machine
- start push button electrical switch
- principle operation of a start button
- start button overload connection
- start and stop button ford escape2014
- start and push button on electricals
- single push button start stop circuits
- on/off motor start buttons
- operation of push pull button circuit using and gate and inverter gate
- purpose of a start and stop switch
- single ph motor on off push button switch
- Start and stop relay switch
- start stop button
- characteristics of types of stop/start retain relay control circuit for an AC motor
- start stop gate
- start stop common button
- operation of start and stop button
- Start stop circuit
- start and stop push buttons
- relay logig control one push button on off motor
- start stop button connection